The ISO 15848 standard is an international standard for the measurement, testing, and identification procedures of fugitive emissions for industrial valves, such as volatile organic compounds (VOCs) and hazardous substance leaks. Its aim is to control the environmental pollution risk of industrial valves by standardizing testing methods and classification systems. This standard is divided into multiple parts, with Part 1 (ISO 15848-1) focusing on the classification system and qualification procedures for valve type testing, and Part 2 (ISO 15848-2) addressing specific requirements for production acceptance testing.
Now let’s see one of our JUDU order that 3 '', CL10000,API 6A mga balbula sa globo, Chemical project’s End User need to do test to meet the 50ppm maximum emission level classification C01 in accordance wth ISO15848-1 and ISO15848-2

Valve details:as per table 1

Valve drawing
Valve Photos:


As per clients request,these 10 pcs mga balbula sa globo, 9pcs need to do fugitive emission as per ISO 15848-2,and 1pc need to do fugitive emission as per ISO 15848-1.
● Preparation:
Valves must undergo ISO 15848-1 type test design validation to ensure that they are tested under design limit temperature and pressure conditions, and to ensure that the packing is dry.
● Test method:
Using the sniffing method (refer to Appendix B of ISO 15848-1), helium gas is used as the test medium (purity ≥ 97%) to measure the leakage concentration (unit: ppmv, 1ppmv=1ml/m ³)
● Test operation:
The globe valve needs to complete a fully closed - fully open - fully closed mechanical cycle test. Verify the stability of sealing performance
●Test Result by TUV:
TUV.R inspector had witnessed the fugitive emission for 1pcs globe vales in accordance with ISO15848- 1:2017. The serial no of selecting valve was JUDU20050309, the details see below:
| item | Test pressure stem seal (MPa) | Leakage of stem seal (PPMV) | resulta | Test pressure body seal (MPa) | Leakage of body seal (PPMV) | resulta | ||||
| Req. | Lihok. | Req. Max. | Lihok. | Req. | Lihok. | Req. Max. | Lihok. | |||
| Temperatura sa kwarto | 61.6 | 61.6 | 50 | 4.06 | OK | 61.6 | 61.6 | 50 | 5.25 | OK |
| Room temperature 50 mechanical cycles | 61.6 | 61.6 | 50 | 5.59 | OK | N / A | N / A | N / A | N / A | N / A |
| 150 ℃ | 25Mpa | 25Mpa | 50 | 5.71 | OK | N / A | N / A | N / A | N / A | N / A |
| 150℃ 50 mechanicalcycles | 25Mpa | 25Mpa | 50 | 5.89 | OK | N / A | N / A | N / A | N / A | N / A |
| Temperatura sa kwarto | 61.6 | 61.6 | 50 | 4.29 | OK | N / A | N / A | N / A | N / A | N / A |
| Room temperature 50mechanical cycles | 61.6 | 61.6 | 50 | 4.25 | OK | N / A | N / A | N / A | N / A | N / A |
| 150 ℃ | 25Mpa | 25Mpa | 50 | 6.63 | OK | N / A | N / A | N / A | N / A | N / A |
| 150℃ 50 mechanical cycles | 25Mpa | 25Mpa | 50 | 5.94 | OK | N / A | N / A | N / A | N / A | N / A |
| Temperatura sa kwarto | 61.6 | 61.6 | 50 | 5.98 | OK | N / A | N / A | N / A | N / A | N / A |
| Room temperature 5 mechanical cycles | 61.6 | 61.6 | 50 | 5.69 | OK | 61.6 | 61.6 | 50 | 5.21 | OK |
● Test Photos:




● Preparation:
Only applicable to valve designs that have passed the ISO 15848-1 type test, ensuring that the valve packing is dry before the test, avoiding moisture affecting the test results, tightening the valve stem seal, and ensuring that the initial sealing performance meets the requirements
● Test method:
The default test pressure is 6 bar and the temperature is room temperature.Using the sniffing method (refer to Appendix B of ISO 15848-1), helium gas is used as the test medium (purity ≥ 97%) to measure the leakage concentration (unit: ppmv, 1ppmv=1ml/m ³)
● Test operation:
Valve stem seal leakage: Measure the initial leakage after the valve is pressurized in a semi open state, and retest after 5 full open and full closed cycles to ensure stable dynamic sealing performance.
Valve body seal leakage: After the pressure stabilizes, detect the leakage at the static seal, and it is required to be lower than the ppmv limit specified in the standard.
● Test Result by TUV:
TUV.R inspector had witnessed the fugitive emission for 9pcs mga balbula sa globo in accordance with ISO15848- 2:2017, and results met the requirements, Details see below:
| Serial Dili | Test pressure stem seal (Mpa) | Leakage of stem seal (PPMV) | Resu lt | Test pressure body seal (Mpa) | Leakage of body seal(after 5 mechanical cycles)(PPMV) | resulta | ||||
| Req | Act | Req Max | Act | Req | Act | Req Max | Act | |||
| JUDU20050301 | 0.6 | 0.6 | 50 | 4.25 | OK | 0.6 | 0.6 | 50 | 6.63 | OK |
| JUDU20050302 | 0.6 | 0.6 | 50 | 5.59 | OK | 0.6 | 0.6 | 50 | 5.71 | OK |
| JUDU20050303 | 0.6 | 0.6 | 50 | 5.08 | OK | 0.6 | 0.6 | 50 | 5.40 | OK |
| JUDU20050304 | 0.6 | 0.6 | 50 | 4.29 | OK | 0.6 | 0.6 | 50 | 6.63 | OK |
| JUDU20050305 | 0.6 | 0.6 | 50 | 5.94 | OK | 0.6 | 0.6 | 50 | 6.78 | OK |
| JUDU20050306 | 0.6 | 0.6 | 50 | 4.5 | OK | 0.6 | 0.6 | 50 | 4.73 | OK |
| JUDU20050307 | 0.6 | 0.6 | 50 | 4.5 | OK | 0.6 | 0.6 | 50 | 4.73 | OK |
| JUDU20050308 | 0.6 | 0.6 | 50 | 4.87 | OK | 0.6 | 0.6 | 50 | 5.69 | OK |
| JUDU20050310 | 0.6 | 0.6 | 50 | 4.44 | OK | 0.6 | 0.6 | 50 | 4.61 | OK |
| Serial Dili | Test pressure stem seal(MPa) | Leakage of stem seal PPM(After 5 mechanical cycles) | ||
| Req. | Lihok. | Req. Max. | Lihok. | |
| JUDU20050301 | 0.6 | 0.6 | 50 | 5.94 |
| JUDU20050302 | 0.6 | 0.6 | 50 | 4.29 |
| JUDU20050303 | 0.6 | 0.6 | 50 | 5.21 |
| JUDU20050304 | 0.6 | 0.6 | 50 | 4.34 |
| JUDU20050305 | 0.6 | 0.6 | 50 | 6.12 |
| JUDU20050306 | 0.6 | 0.6 | 50 | 4.61 |
| JUDU20050307 | 0.6 | 0.6 | 50 | 4.61 |
| JUDU20050308 | 0.6 | 0.6 | 50 | 5.18 |
| JUDU20050310 | 0.6 | 0.6 | 50 | 4.50 |
● Test Photos:


● Priority selection of ISO 15848-1
Valves need to be used for high-risk media such as highly toxic, flammable, and explosive fluids;
Must meet international certification requirements (such as EU CE, T Ü V certification);
During the design phase, it is necessary to verify long-term durability (such as the 610 mechanical cycles required by API 624)
● Priority selection of ISO 15848-2
Rapid acceptance is required during mass production (such as sampling at least 1 unit per batch);
The valve has passed ISO 15848-1 certification and only needs to verify the consistency of the leakage rate;
Cost sensitive and low-risk operating conditions (such as ordinary industrial fluids).
Ang pagpili sa materyal para sa mga balbula nga taas og temperatura ubos sa mga kondisyon sa pag-operate gikan sa 550°C hangtod 1100°C nanginahanglan og komprehensibo nga pagkonsiderar sa mga hinungdan lakip ang temperatura, presyur, medium nga kinaiya ug gasto. Ang kinauyokan nga prinsipyo mao nga ang materyal...
Kon magtrabaho ka gamit ang mga tubo ug pluwido sa mga pabrika o industriya, importante kaayo ang pagpili sa husto nga balbula. Duha ka kasagarang klase mao ang gate valve ug globe valve. Ang matag usa adunay kaugalingong espesyal nga kinaiya. Ang gate valve maayo alang sa hingpit nga pag-abli o pagsira sa linya, l...
Ang pressure control valve usa ka importante nga parte sa daghang mga makina ug setup. Makatabang kini sa pagdumala sa presyur sa mga likido o gas sulod sa mga tubo. Kung ang presyur motaas pag-ayo, kini mahimong hinungdan sa mga problema sama sa pagtulo o bisan pagbuto. Ang balbula mogana pinaagi sa awtomatikong pag-adjust sa fl...
Ang balbula sa alibangbang ginganlan gikan sa espesyal nga porma niini. Kon imong tan-awon ang sulod sa balbula, adunay patag nga disc nga nagtuyok palibot sa usa ka rod. Kini nga disc molihok balik-balik, sama sa pako sa alibangbang kon kini moabli ug mosira. Ang disenyo nagtugot kanimo sa pagkontrol sa pag-agos sa pluwido...